DC charging means the car receives direct current. On most sites the solar, the battery, and the charger still meet on the AC board. The charger does not follow the panels by itself.
Two ways to draw the same car
Solar leaves its inverter as AC. The battery leaves its own inverter as AC. The grid fills whatever the cars still need. The ST-DC30 takes AC from that board and hands DC to one car. Nothing in that chain tracks the solar curve unless a separate energy manager is specified, and ShineTong does not make that manager.
A shared DC bus keeps PV, the battery, and the charger on direct current and converts to AC only at the grid. That saves a conversion, and it needs DC protection, a bus voltage everyone agrees on, and one controller. It is a different project from bolting an ST-DC30 onto an AC board.
Power stacks. Energy is the easier half.
One ST-DC30 is 30 kW to one connector pair. A second car at the same moment needs a second charger, or it waits. Two cars at 30 kW is 60 kW on the board while they overlap. The kilowatt-hours they eventually take can still fit a smaller supply, because they do not all arrive full and leave empty in the same minute.
That overlap is why storage is on the drawing. A LiFePO4 pack can carry part of the spike and recharge when the bays are empty. The pack size is a project number. There is no public ShineTong price and no standard kWh to paste in.
The same split is written out in how a PV, storage and EV station works.
What is actually supplied
ShineTong supplies the DC charger and LiFePO4 storage. The PV inverter, the battery inverter, and the site controller are specified with the project. They are not inside the ST-DC30.
Load balancing on the ST-AC22 is a shared cap across its two Type 2 outputs. It is not solar tracking, and it is not on the DC charger.
If the car does not need DC
| Charger | Output | What the card actually lists |
|---|---|---|
| ST-AC07 | 7 kW / 32 A, Type 2, IP65 | Wi-Fi and the app. 32 A at 7 kW lines up with a single-phase circuit. |
| ST-AC11 | 11 kW / 16 A, Type 2 socket, IP65 | The card that lists RFID and OCPP. 16 A at 11 kW lines up with three-phase, not a 16 A single-phase socket. |
| ST-AC22 | 22 kW as 11 kW × 2, dual Type 2, IP54 | Load balancing between the two outputs. A shared cap, not a solar follower. |
| ST-DC30 | 30 kW DC, CCS2 / CHAdeMO | Efficiency above 95%, 7-inch touchscreen. One DC output, not two. |
The charger page states OCPP 1.6J. That is a network protocol for the charger and a management platform. It does not move solar into the car. OCPP 2.0.1 is not what that page states.
Send the bay count and the hour they overlap
How many cars, whether they need DC, the supply voltage, and whether a LiFePO4 pack is meant to shave that hour. We will quote the charger and the storage, and we will name the inverter and the controller as someone else’s scope.